Parameter | Details |
Technology | True ON -LINE IGBT based, Microprocessor Controlled Double conversion technology, ISOLATION AT output |
Input | Voltage 130 - 300 Volts, 1Ph |
Input Frequency 40 - 70 Hz, rectifier- IGBT based All generator compatible |
Input power factor of UPS > 0.8 |
Output | Voltage 230 volts, 1 phase + 1%, Independent of input |
Power factor 0.8 lag to unity |
Frequency is Constant 50 Hz crystal generated frequency |
Crest Factor> 3:1 |
Waveform | Pure Sine Wave |
Total Harmonic Distortion (THD) < 3% For Linear Load |
THD < 5% for Non -linear load |
Overload Rating | 110% for 30 minutes 125% for 20 minutes 400% for 0.05 seconds (Tripping sensing 500mili sec) |
Transient Response | For 0 -100 % load change value remains between 5% & recovery is within 20 mili seconds (2 cycles) |
Efficiency at full load | Inverter efficiency greater than 91 % |
Over all efficiency greater than 85% |
Protection | Surge Protection & Noise Filtering |
EMI / RFI filters at input & output side |
Tripping when sparking at load side / ups output with in 20 mili sec i.e one cycle. |
Tripping when short-circuiting at load side / ups output with in 20 mili sec i.e one cycle. |
Input AC over voltage (up to 600V) / Under voltage/ Auto recovery no damages to UPS & load |
DC Over voltage/Under voltage, Over Temperature. Over Current for Rectifier |
Output over voltage, under voltage |
Output overload , Short Circuit |
Over Current for Rectifier |
Isolation Transformer at output side |
Switch Gear | MCB for mains, MCB for Battery, UPS circuitry works as protection breaker for Load Highly sensitive and operates with in 1-2 cycles |
Audio Alarm | Rectifier trip |
Over load |
Pre alarm |
System trip |
Mains Fail |
Battery Low |
Indication | Mains On / Failed LED |
Battery On / Low LED |
| Inverter on / trip LED |
Display | Input Voltage/ Output Voltage Digital display |
Current (input/output) -Digital display |
Frequency (Input/output) - Digital display |
Battery Specification | Back-up time greater than 30 minutes at half load, greater than 10 min at Full load |
Maintenance free, leak proof sealed lead acid battery |
Battery to be in-built in UPS frame. Constant voltage with current limit. |
Battery to be only of standard/recognized makes like Excide, Global Yuasa, AMAR RAJA only |
Environment | Environment Operating Temperature range from 0-50 deg. C |
Humidity up to 95 % RH (Non -Conducting) |
Cooling - Forced Air Cooling |
Noise - Less than 55 db at 1 meter |
Warranty | 2 years on-site warranty with replacement with proper working UPS. No repair at site. And warranty for Batteries is one year |