| Parameter | Details |
| Technology | True ON -LINE IGBT based, Microprocessor Controlled Double conversion technology, ISOLATION AT output |
| Input | Voltage 130 - 300 Volts, 1Ph |
| Input Frequency 40 - 70 Hz, rectifier- IGBT based All generator compatible |
| Input power factor of UPS > 0.8 |
| Output | Voltage 230 volts, 1 phase + 1%, Independent of input |
| Power factor 0.8 lag to unity |
| Frequency is Constant 50 Hz crystal generated frequency |
| Crest Factor> 3:1 |
| Waveform | Pure Sine Wave |
| Total Harmonic Distortion (THD) < 3% For Linear Load |
| THD < 5% for Non -linear load |
| Overload Rating | 110% for 30 minutes 125% for 20 minutes 400% for 0.05 seconds (Tripping sensing 500mili sec) |
| Transient Response | For 0 -100 % load change value remains between + 5% & recovery is within 20 mili seconds (2 cycles) |
| Efficiency at full load | Inverter efficiency greater than 91 % |
| Over all efficiency greater than 85% |
| Protection | Surge Protection & Noise Filtering |
| EMI / RFI filters at input & output side |
| Tripping when sparking at load side / ups output with in 20 mili sec i.e one cycle. |
| Tripping when short-circuiting at load side / ups output with in 20 mili sec i.e one cycle. |
| Input AC over voltage (up to 600V) / Under voltage/ Auto recovery no damages to UPS & load |
| DC Over voltage/Under voltage, Over Temperature. Over Current for Rectifier |
| Output over voltage, under voltage |
| Output overload , Short Circuit |
| Over Current for Rectifier |
| Isolation Transformer at output side |
| Switch Gear | MCB for mains, MCB for Battery, UPS circuitry works as protection breaker for Load Highly sensitive and operates with in 1-2 cycles |
| Audio Alarm | Rectifier trip |
| Over load |
| Pre alarm |
| System trip |
| Mains Fail |
| Battery Low |
| Indication | Mains On / Failed LED |
| Battery On / Low LED |
|
| Inverter on / trip LED |
| Display | Input Voltage/ Output Voltage Digital display |
| Current (input/output) -Digital display |
| Frequency (Input/output) - Digital display |
| Battery Specification | Back-up time greater than 30 minutes at half load, greater than 10 min at Full load |
| Maintenance free, leak proof sealed lead acid battery |
| Battery to be in-built in UPS frame. Constant voltage with current limit. |
| Battery to be only of standard/recognized makes like Excide, Global Yuasa, AMAR RAJA only |
| Environment | Environment Operating Temperature range from 0-50 deg. C |
| Humidity up to 95 % RH (Non -Conducting) |
| Cooling - Forced Air Cooling |
| Noise - Less than 55 db at 1 meter |
| Warranty | 2 years on-site warranty with replacement with proper working UPS. No repair at site. And warranty for Batteries is one year |